The CO48 Powered Process Totaliser is a programmable instrument that has been designed to accept pulses from open collector, hall affect, turbine meters or 24VDC voltage pulse. The input measurement is shown on either a high contrast eight (8) digit LED or LCD display.
Make an enquiryThe instruments incorporate field programmable totalising rates and a 24VDC isolated supply for powering remote sensors. The CO48 is supplied in a panel mount 48 x 96 mm enclosure. Screw terminal electrical connection is included.
Input Type | sw1 | sw2 | sw3 | sw4 | Sw5 | sw6 | sw7 | sw8 | |
A | CMOS Logic Level | Off | Off | Off | Off | On | Off | Off | off |
B | Open collector or reed switch | Off | Off | Off | Off | On | Off | On | off |
C | Namur proximity [loop supply 8VDC] | Off | Off | On | On | On | Off | Off | off |
D | Reed switch with debounce | Off | Off | Off | Off | On | Off | On | On |
E | Coil 50mV PP minimum | Off | On | Off | Off | Off | Off | Off | off |
F | Low impedance coil 50mV PP min. | On | On | Off | Off | Off | Off | Off | off |
Terminal 1:Input 0VDC (-) | Terminal 7:relay one normally open contact |
Terminal 2:Input minus (-) | Terminal 8:relay one normally closed contact |
Terminal 3:Input plus (+) | Terminal 9:relay one common contact |
Terminal 4:24VDC loop supply (+) | Terminal 10:VAC active or VDC (+) supply |
Terminal 5: reset | Terminal 11:VAC neutral or 0VDC (-) supply |
Terminal 6: not used | Terminal 12:Ground supply |