The IBC Batch Controller is a 120/240VAC or 12-40VDC powered batch controller for liquids that incorporates an eight (8) digit 14.2mm LED (light emitting diode) display. The instrument can be configured from the front touch buttons to batch volumes from 0.001 to 999,999 litres and K factors from 999,999 to 0.01 can be utilised. The instrument can batch in up or down mode and provide the excitation power supply for the flow sensor.
Make an enquiryIBC Batch Controller is a 120/240VAC or 12-40VDC powered batch controller for liquids that incorporates an eight (8) digit 14.2mm LED (light emitting diode) display. The instrument can be configured to batch volumes from 0.001 to 999,999 litres and K factors from 999,999 to 0.01. The instrument can batch up or down and provide the excitation power supply for the flow sensor.
The IBC can operate in local manual mode by front panel touch switches for Batch Start, Stop and Resume or in remote mode as these functions are available for external control.
The instrument accepts an input from 0 to 5KHZ and is dip switch selectable for open collector, reed, Hall, Namur and turbine signals (from 20mV peak to peak).
Input Type |
sw1 |
sw2 |
sw3 |
sw4 |
sw5 |
sw6 |
sw7 |
sw8 |
|
A |
CMOS Logic Level |
Off |
Off |
Off |
Off |
On |
Off |
Off |
off |
B |
Open collector or reed switch |
Off |
Off |
Off |
Off |
On |
Off |
On |
off |
C |
Namur proximity [loop supply 8VDC] |
Off |
Off |
On |
On |
On |
Off |
Off |
off |
D |
Reed switch with debounce |
Off |
Off |
Off |
Off |
On |
Off |
On |
On |
E |
Coil 50mV PP minimum |
Off |
On |
Off |
Off |
Off |
Off |
Off |
off |
F |
Low impedance coil 50mV PP min. |
On |
On |
Off |
Off |
Off |
Off |
Off |
off |
The IBC incorporates an eight (8) digit 14.2mm digit height high contrast (LED) display with a wide viewing angle and a viewing distance of 5 metres.
The instrument incorporates a background running total that is stored in eeprom memory during loss of power. This total can be displayed by the front total touch button and reset by a normally open push button between terminals 1 and 7.
The instrument incorporates a low flow alarm. If no input pulses are received in a pre- programmed period the low flow output becomes active and the batch is cancelled and LF ERR is displayed.
Terminal 1:Input Common (-) |
Terminal 11:End of batch open collector output |
Terminal 2:Input minus (-) |
Terminal 12:Relay one normally open contact |
Terminal 3:Input plus (+) |
Terminal 13:Relay one normally closed contact |
Terminal 4:Start |
Terminal 14:Relay one common contact |
Terminal 5:Stop |
Terminal 15:Relay two normally open contact |
Terminal 6:Resume |
Terminal 16 Relay two normally closed contact |
Terminal 7:Reset |
Terminal 17:Relay two common contact |
Terminal 8:24VDC sensor supply |
Terminal 18:85 to 265VAC /24VDC active supply: |
Terminal 9:Open collector pulse output per litre |
Terminal 19: VAC neutral or 0VDC supply (-) |
Terminal 10:Low flow alarm open collector output |
Terminal 20:Ground supply |